SKU: ENL-IAQ-R
The enLink IAQ Radon Sensor series by Synetica, offering continuous, real-time tracking of harmful Radon gas, powered by LoRaWAN.
Details Data Sheet Manual
Variants:
The enLink IAQ Radon Monitor by Synetica offers continuous, real-time tracking of radon, a naturally occurring Radon gas that can seep into buildings undetected. Because it builds up in enclosed areas and presents a severe, long-term health hazard, accurate and dedicated testing is vital to spot this invisible, tasteless, and odourless threat.
Constructed using Synetica’s established indoor air quality framework, this device pairs a dependable monitoring system with a specialised radon sensor.
Ideal for applications, such as:
| Product Name | Product Code | Monitored Parameters |
|---|---|---|
| Synetica enLink Radon Sensor | ENL-IAQ-R | Radon |
| Synetica enLink Radon Sensor with CO2 | ENL-IAQ-RC | Radon, CO2 |
| Synetica enLink Radon Sensor with CO2 & Particulate Matter | ENL-IAQ-RCP | Radon, CO2, Particulate Matter |
| Core Sensing | |
|---|---|
| Temperature Accuracy | ±0.2°C (Typical) |
| Temperature Repeatability | ±0.1°C |
| Temperature Response Time (τ63%) | 2 s |
| Humidity Accuracy | ±1.8% RH (Typical) |
| Humidity Repeatability | ±0.25% RH |
| Humidity Response Time (τ63%) | 4 s |
| Barometric Pressure Accuracy | ±0.12 hPa |
| Pressure Full-Accuracy Range | 300 to 1100 hPa |
| Pressure Resolution | 0.18 Pa |
| Air Quality & Radon | |
| VOC Monitoring | Continuous (IAQ Index & TVOC Output) |
| IAQ Index Range | 0 to 500 |
| TVOC Output | ppm |
| VOC Response Time | 1 s |
| Radon Measurement Range | 3.3 Bq/m³ – 37 kBq/m³ (0.09–1,000 pCi/L) |
| Radon Sensitivity | 0.2 cpm / 1,000 Bq/m³ |
| Radon Response Linearity | ±2.5% |
| Data Update Interval | 1 Hour |
| Integration Windows | 6h, 12h, 24h, 48h, 72h, 96h, total average |
| Optional Sensors | |
| CO² Sensor Type | NDIR (Air quality & ventilation) |
| CO² Accuracy | ±(30 ppm + 3% of reading) |
| CO² Range | 0 to 5,000 ppm (Standard), 0 to 10,000 ppm (Extended) |
| CO² Response Time (τ90) | 3 minutes |
| Particulate Matter Sensor | Laser-based light scattering (MCERTS-certified) |
| PM Sizes Measured | PM0.5, PM1, PM2.5, PM4, PM10 |
| PM Concentration Range | 0 – 1,000 μg/m³ |
| PM1 & PM2.5 Accuracy | 0-100 μg/m³: ±5 μg/m³ +5% m.v. | 100-1000 μg/m³: ±10% m.v. |
| PM4 & PM10 Accuracy | 0-100 μg/m³: ±25 μg/m³ | 100-1000 μg/m³: ±25% m.v. |
| PM Mass Resolution | 1 μg/m³ |
| PM Lower Detection Limit | 0.3 μm |
| PM Response Time (τ90) | < 6 s |
| Family | ENL-IAQ-R Series |
| Application | Indoor Air Quality (IAQ) & Radon Monitoring |
| Standard Sensors | Temperature, Humidity, Pressure, VOCs, Radon |
| Optional Configuration | CO², Particulate Matter (PM1, PM2.5, PM10) |
| Radon First Data Display | 6 Hours |
| Detection Environment | -10°C to 45°C |
| Humidity Environment | RH < 90% |
| Certifications | MCERTS (Particulate Matter sensor) |
| Reliable Radon Measurement Readiness Time | |
|---|---|
| High Levels (> 190 Bq/m³) | 6 Hours |
| Medium Levels (94–190 Bq/m³) | 12 Hours |
| Low Levels (< 94 Bq/m³) | 24 Hours |
All of our products are available to customers throughout Europe. For more information on shipping costs, currency conversions and lead times, please contact our technical sales team. Our technical sales team are also happy to advise customers on the best LoRaWAN® People Counting sensors to suit specific project requirements.